The main objective of Rain Defence Louvres is to allow the passage of air, whilst providing the area beyond the room with protection from rain penetration.
When specifying rain defence louvres we recommend comparing the airflow class and the level of rain defence provided by the louvre.
Our CS RS-5605 rain defence louvre offers the best combination of airflow, rain defence and spatial efficiency of any product on the market.
Why CS Rain Defence Louvres
- industry leading performance characteristics
- unparalleled global experience
- worldwide technical support
- first class innovation & designs
- most spatially efficient models on the market
- up to 100% rain defence with some models
- robust blades up to 3x thicker than rolled blades
- up to date, relevant test information
Louvre pressure drop is one of the key parameters of establishing the louvre requirements for your project as it’s based on the needs of the building and its ventilation system, rather than “free area” which doesn’t really mean anything.
Pressure drop is defined as the pressure differential from one side of a louvre to the opposite side, often expressed in Pascals (Pa). Louvre pressure drop occurs when frictional forces, caused by the resistance to flow, act on air moving through a louvre.
Increased louvre pressure drop can prevent equipment inside the ventilated area drawing sufficient air through the louvre, resulting in overheating, as the equipment has to work harder to draw the air through.
Guidance
Air Density (ρ)
is generally 1.225 kg/m³ (at sea level)
Volumetric Flow (qv)
is supplied by the ventilation engineer and relates to the amount of air required through the system
Core Area (A)
The minimum height times the minimum width of the front opening in a louvre assembly with the louvre blades removed.
Discharge Loss Coefficient (CD)
See chosen louvre model testing information.
Discharge Loss Guidance
Louvre Model | Penetration Class | Airflow Class | Discharge Loss Coefficient |
---|---|---|---|
RSH-5700 | A up to 3.0m/s | 3 | 0.289 |
RSV-5700 | A up to 3.5m/s | 3 | 0.297 |
RS-5605 | A up to 3.5m/s | 1 | 0.466 |
A-3105 | D up to 3.5m/s | 2 | 0.391 |
A-4080 | C up to 1.0m/s | 2 | 0.38 |
A-4085 | C up to 1.0m/s | 2 | 0.38 |
La perte de charge est un paramètre essentiel dans la spécification d’une grille pour la ventilation d’un ouvrage. Ce résultat se base sur l’analyse des besoins en ventilation du bâtiment plutôt que la surface libre offerte, qui n’a pas d’intérêt aéraulique pour la structure.
La perte de charge résulte de la différence de pression constatée de part et d’autre de la grille. Exprimée en Pascal (Pa), la perte de charge dite linéaire est due aux frottements du flux d’air lors de son passage au travers des lames des grilles.
Si la perte est trop importante le flux d’air amené et requis par des équipements de ventilation, comme des CVC, sera insuffisant. Dès lors, les équipements demanderont plus d’énergie pour faire transiter l’air dans le réseau de ventilation, mais aussi pour se refroidir.
Guide
- La densité ρ = 1,225 kg/m3. Elle correspond à la densité de l’air sec au niveau de la mer à la température de 15°C.
- Débit volumique de ventilation en m3/s (qv) Cette donnée est fournie par l’ingénieur en charge de la ventilation et correspond au volume d’air ventilé requis pour le projet.
- Surface nette d’aération exprimé en m² (A) Cette donnée est propre à chaque grille de ventilation et est fournie dans ses spécifications.
- Coefficient de performance aéraulique Cette donnée est propre à chaque grille de ventilation et est fournie dans ses spécifications.